Scenario · Utility restoration
The Feeder That Could Not Be Restored Yet
Laila's plan to restore two segments looks workable, but it remains blocked until Mateo supplies current field clearance and the responsible operator authorizes the switching request.
- What this is
- A published decision scenario. Its setting and values are invented for illustration.
- What this shows
- How declared facts and rules produce a traceable result when conditions change.
- What this does not show
- A customer deployment, measured outcome, or transfer of authority to software.
Narrated film · 1:10
The Feeder That Could Not Be Restored Yet
See why a restoration plan must stop when its evidence changes, until the authorized operator has what they need.
1:10
Story
Start with the event and the decision it creates.
The story
18:06 — one protective operation changes three local truths
At 18:06, Feeder 27 trips during a windstorm. Laila Morgan, Ridgeline Electric's distribution system operator, sees the protection source report the breaker open in a protection-lockout state. That source state is not worker protection, field clearance, or permission to switch. The exact records are protection event PROT-771 and outage case OUT-402, which initially associates 3,420 synthetic service points with the interruption across North, Central, and River.
Laila's goal is to determine whether North and River can enter a partial-restoration proposal while damaged Central remains held out. Mateo Ruiz owns the field-clearance evidence she will need. The outage clock has started for all 3,420 represented service points, but neither urgency nor a green map can supply the missing safety evidence.
The initial records are consequential and narrow. They do not establish what caused the trip, whether equipment is damaged, whether any conductor is safe, where a work boundary exists, or when service can return. Grid records the source-reported event and starts evaluating dependencies without filling in those missing truths.
18:09 — a plausible topology appears
The authored topology suggests a possible future configuration: after separately authorized external switching, North would return from the Feeder 27 source, River would transfer through a tie to source F31, and damaged Central would remain held out. This is a proposal to screen, not the current topology or a switching sequence.
The Scenario deliberately uses only a simple authored screen:
| Segment | Synthetic service points | Proposed treatment | Simple authored screen | Result |
|---|---|---|---|---|
| North | 1,480 | Return from F27 | 1.20 × 1.25 = 1.500 MW ≤ 1.65 MW |
Pass |
| Central | 1,160 | Hold out | 0.92 MW; no pickup is screened | Remains out |
| River | 780 | Transfer through F31 | 0.58 × 1.25 = 0.725 MW ≤ 0.82 MW |
Pass |
The screened proposal covers 2,260 of 3,420 service points, displayed as 66.1 percent under the fixture's declared rounding rule. The capacity screen passes. That result is not a power flow, protection study, switching instruction, safety conclusion, authorization, execution report, or restoration count.
18:14 — the plan depends on a pre-event fact
The selected record for isolation point SW-27-4 says open, but its observation time is 18:05:51—twenty seconds before the feeder trip. The outage system has derived an isolated label from that and another device indication.
Grid keeps the supporting facts visible while blocking the favorable conclusion. A symbol on a map is not field clearance. A topology label cannot prove that Ridgeline's external employee-protection conditions have been completed.
18:16–18:23 — a field-link gap returns with a contradiction
Mateo Ruiz, the employee responsible for clearance CLR-731, loses the field connection for seven minutes. His crew continues under Ridgeline's external procedure. The control-center model sees only the age of its last accepted field evidence; it neither directs the crew nor invents an update.
During the gap, the device adapter redelivers the original SW-27-4 event. The source event ID and 18:05:51 observation time are unchanged. The duplicate is ignored and does not refresh the observation; recent receipt cannot repair stale evidence.
When the connection returns, Mateo reports that the local position indication is insufficient to establish the work-zone boundary and that damaged conductor is visible inside the held-out Central segment. The outage-system label supports a favorable isolation conclusion; the field report refutes it. The evidence is contradictory, so the represented policy blocks the proposal.
The model does not average away the disagreement or decide that one source always outranks another. The disagreement is the decision-relevant state.
18:25 — three alternatives expose the stopping point
The fixture evaluates exactly three defined alternatives:
| Alternative | Result | Why |
|---|---|---|
| Return all three segments from Feeder 27 | Rejected | The Central damage and isolation gate remain unresolved. |
| Transfer North and River together through F31 | Rejected | (1.20 + 0.58) × 1.25 = 2.225 MW, above the authored 0.82 MW tie headroom. |
| Hold Central out, return North from F27, and transfer River through F31 | Conditional | The simple load screens pass, but current clearance evidence is still missing. |
Completing that small search does not prove the topology complete, find a global optimum, or make the third plan electrically feasible or safe. It only explains why one authored proposal survives farther than the other two.
18:37 — external clearance evidence changes what may be proposed
Between 18:23 and 18:37, Mateo and Ridgeline's system operator complete the utility's external field and safety process. Grid neither encodes nor instructs those steps. At 18:37, that process produces attributable report CLR-731-R4, bound to the held-out Central zone, responsible employee, procedure revision, source time, and external system record.
That report changes the isolation evidence from unresolved to supported. It does not release the clearance, energize equipment, or authorize the partial plan. It permits the model to assemble a packet for the person who holds the next authority.
18:40–18:47 — human authority and external execution remain separate
Laila reviews packet RESTORE-PACKET-220, which binds the protective event, current topology, Mateo's clearance report, the surviving alternative and its arithmetic, the held-out Central boundary, unresolved assumptions, external validation sources, and stop conditions.
Laila authorizes external switching order SO-220 under Ridgeline's represented policy. Her assertion records the decision on one exact packet. It does not move a switch.
The external DMS acknowledges the request at 18:40:08. It has received the request; it has not proved execution. Later SCADA and field reports describe external work, while protection, meter, and outage sources support later device and service states. Only after the source-defined outage aggregate arrives does the model publish the source's initial label: 2,260 restored / 1,160 remaining. Even then, that aggregate does not prove that every premise, device, or person has service or is safe.
19:04 — the restoration count is corrected
Meter exception revision METER-552 reports sixteen synthetic River service points still without service because of a separate secondary condition. The current figures become:
restored = 2,260 - 16 = 2,244
remaining = 3,420 - 2,244 = 1,176
displayed restored share = 65.6%
The correction does not undo Laila's earlier authorization or prove it was wrong. It changes the current outage state, adds follow-on work, and makes the first operations summary and public-update draft stale. Their successors must use 2,244 while retaining the lineage back to the initial source report.
The opening question therefore has a bounded answer. The capacity screen remained conditional until a current external clearance report made the partial plan reviewable. Laila's authorization enabled only an external request; later source reports separately described work and corrected the service count. None of those states establishes electrical safety, complete restoration, or a public outcome.
Why this setting is recognizable
The U.S. Department of Energy's public restoration overview describes utilities maintaining plans to restore electricity safely after outages. DOE's Power System Data Analytics describes measurement, processing, display, system visibility, and operator-support tools. OSHA's electric power generation, transmission, and distribution standard distinguishes relevant system-operator and employee-in-charge responsibilities and addresses controlled deenergizing, clearance, and reenergization within its applicability.
Those official sources ground only the high-level restoration, operator-support, and clearance context. They do not establish Ridgeline's topology, calculations, facts, authority delegation, switching sequence, Grid composition, or result. Actual applicability, system state, procedure, engineering, and safety judgments belong to the responsible utility and qualified professionals.
Where the model stops
Grid can represent selected evidence, freshness, contradiction, declared alternatives, a synthetic capacity screen, an exact packet, and correction lineage. It cannot determine electrical truth, perform power flow or protection analysis, establish deenergization or clearance, issue or execute switching, direct a crew, release a clearance, energize a feeder, certify restoration, or publish a public outcome.
This public page contains no real utility, location, voltage, coordinate, control endpoint, protection setting, credential, customer record, or crew location. It is not an operational diagram and must not be adapted into switching guidance.
What remains to prove
Source revision 2026-08-27.1 has reviewed domain context, product boundaries, and a public-suitability finding, so this authored, non-operational scenario can be published at R2. The fixture itself remains authored.
The next proof is an exact deterministic implementation of the three segments, calculations, stale indication, seven-minute link gap, duplicate, contradiction, clearance state, three alternatives, authority stop, external evidence states, and sixteen-service-point correction. It needs a separately identified independent oracle reviewer, retained execution and verification evidence, negative cases, and a high-consequence assurance review. Any intended-environment work would additionally require utility-owned engineering, safety, cybersecurity, identity, delegation, source, control, records, accessibility, reconciliation, and operator qualification. No later readiness label can turn this editorial fixture into a switching procedure or electrical safety claim.
Decision path
Follow the changed fact step by step.
A calculation, proposal, approval, execution report, and outcome are different events. The order keeps those boundaries visible.
- 01 · 18:06
One protective operation changes three local truths
Feeder 27 opens into a protection-lockout state, all three synthetic segments enter outage evaluation, and cause, equipment condition, field clearance, and restoration remain unresolved.
- 02 · 18:09
A plausible topology appears
North and River each pass a simple authored pickup screen while damaged Central remains held out, yielding a capacity result—not a safety or restoration conclusion.
- 03 · 18:14
The plan depends on a pre-event fact
One selected open indication predates the trip, and an outage-system isolation label cannot substitute for current field clearance.
- 04 · 18:16–18:23
A field-link gap returns with a contradiction
Duplicate delivery cannot refresh the stale observation, and Mateo's later field report refutes the favorable current-clearance conclusion.
- 05 · 18:25
Three alternatives expose the stopping point
Restoring all segments and loading both candidates onto the tie fail; the partial plan remains conditional because its clearance evidence is missing.
- 06 · 18:37
External clearance evidence changes what may be proposed
A current, attributable clearance report supports the held-out boundary without releasing the clearance, energizing equipment, or authorizing switching.
- 08 · 19:04
The restoration count is corrected
Meter evidence reduces the source-reported restored count from 2,260 to 2,244 and advances current views without rewriting the authorization record.
Evidence and limits
What the scenario represents—and what real-world use still requires.
Represented in this scenario
- Time-qualified device, outage, field, clearance, decision, execution, and correction evidence with explicit ownership
- The synthetic capacity screen, contradictory evidence, bounded alternatives, rejected reasons, and affected derivative cone
- Proposal, clearance evidence, switching authorization, request acknowledgment, reported execution, service validation, and public status as distinct states
Required integration and operating work
- Author and qualify utility-owned schemas, topology, source precedence, adapters, identity and delegation, operator experience, records, accessibility, security, reconciliation, and correction workflow
- Implement the deterministic fixture, freeze an independent oracle, test stale, duplicate, contradictory, expired-clearance, unauthorized, indeterminate, and corrected paths, and retain exact execution, verification, and high-consequence assurance evidence
Decisions that remain with people and institutions
- Field clearance, switching, energization, crew action, protection behavior, or release of a clearance
- Electrical feasibility, deenergization, safety, execution, or service restoration
- Outage communication, customer status, reliability result, legal conclusion, or public outcome
Evidence, authority, and publication recordView the scenario contract, capability record, authority stages, verification status, and related work.
Scenario contract
The setting, trigger, decision, and authority boundary.
- Setting
- Ridgeline Electric, an invented distribution utility serving the invented Pine River district during one windstorm outage.
- Timeframe
- 18:06 through 19:04 during the scenario's restoration period
- Trigger
- Feeder 27 trips and the preferred partial-restoration plan depends on one isolation point whose apparent open status predates the trip.
- Decision
- Whether any bounded partial-restoration alternative may be presented for authorization while the damaged Central segment remains held out.
- Authority
- Grid may join evidence, run the authored screen, and assemble a proposal; Mateo Ruiz owns the represented field-clearance evidence, Laila Morgan owns switching authorization, and external utility systems, qualified crews, meter and outage systems, and the public-information officer retain execution, observed-state, and publication authority.
Feasible is not ready
The capacity screen passes before the safety evidence does.
A simple modeled comparison, stale indication, field contradiction, current clearance, human decision, external work, and corrected count remain distinct.
- SourcesDevice, outage, and field revisions
Observation time and source ownership determine whether a fact is current for this scenario decision.
- ModelTwo pickup screens pass
North at 1.500 MW and River at 0.725 MW fit authored limits without establishing electrical feasibility or safety.
- EvidenceIsolation remains unresolved
A stale open indication and field refutation block the favorable conclusion until external clearance evidence arrives.
- Human authorityExact switching decision
Laila may authorize one represented packet under the authored policy; Grid cannot issue or perform switching.
- External evidenceWork, validation, and correction
Request acceptance, reported device state, outage aggregation, and meter correction answer different questions.
What is established
What is documented, what this scenario combines, and what still needs testing.
This separates documented capabilities from authored combinations in the scenario. Neither proves a complete deployment or outcome.
Documented building blocks
Capabilities described in maintained Grid documentation or another named source.
- Reviewed product primitives document reactive values and bindings, predicates, provenance, ordered streams, connector contracts, governed artifacts, and multiple surfaces within their stated limits; they do not establish a utility-restoration product or safety case.
- Reviewed product primitives document ways to represent revisioned observations, stale and contradictory evidence, an affected dependency cone, and retained decision artifacts; they do not provide power flow, protection analysis, field clearance, switching authority, control, or restoration evidence.
Combined in this scenario
Capability combinations represented in this scenario that still require end-to-end evaluation.
- The authored Scenario composes a synthetic three-segment topology, source-precedence policy, simple MW screens, three bounded alternatives, a clearance pointer, an operator packet, and a correction-capable outage view.
- Utility-owned adapters and experiences would be needed to connect selected SCADA, DMS, OMS, field, protection, meter, decision, execution, and communications records without centralizing their authority.
Not yet proved
Integration, operating, policy, or evidence work that is not complete.
- No package-owned executable fixture, independent oracle, negative-case suite, retained execution and verification record, derivative-parity review, or high-consequence assurance review has yet established the authored behavior.
- No qualified electrical study, safety procedure, utility identity and delegation, SCADA, DMS, OMS, field-work, meter, switching, communications, cybersecurity, or target-environment integration exists, and no observed customer or operational outcome exists.
Proof and limits
What this scenario supports—and what remains to validate.
These states describe the scenario source and its defined checks. Real-world validation requires separate evidence.
- Scenario publication
- PublishedReleased August 27, 2026 as an operating scenario.
- Source readiness
- R2 · Sources reviewedDomain support and product capability boundaries have been reviewed.
- Scenario check
- Checks not runScenario revision 2026-08-27.1 defines the steps and expected results; the checks have not run yet.
- Independent review
- PendingThe expected results have not received independent review.
- Deployment evidence
- NoneNo customer deployment, production performance, or real-world outcome is claimed.
- Next proof required
- Advance beyond R2Run the defined checks, retain the results, and have an independent reviewer check the expected results.
Evidence and stewardship
What supports this scenario—and when it must be reviewed again.
Illustrative evidence
Authored, non-operational utility scenario grounded by reviewed DOE and OSHA sources; it is not a switching order, electrical model, safety procedure, outage estimate, customer deployment, or measured Grid outcome.
Invented elements. Ridgeline Electric and every person, feeder, device, topology, load, service point, time, clearance, order, and outcome are invented. Official sources ground only the high-level restoration and clearance context, and reviewed Grid documents support only generic primitives—not this composition, electrical feasibility, safety, control, deployment, or result.